The mounting plate is connected to the control cabinet frame, PE rail and shield support
through a lar
ge surface area to establish a good electrical connection.
For screwed connections on painted or anodized surfaces, establish a good electrical
connection by using one of the following methods:
Serrated contact washers that cut through the painted or anodized surface
The insulating coating (e.g. paint) at the contact locations has been removed.
4.8.3 Potential equalization between control cabinets
Description
EMC-compliant potential equalization between control cabinets is structured as follows:
The PE rail runs through all control cabinets without any interruption.
The frames of the control cabinets are connected at multiple locations using serrated
washers through a large surface area to establish a good electrical connection.
In systems where the control cabinets are lined up next to one another, and which are
installed in two groups back to back, the PE rails of the two cabinet line-ups are connected
with one another at multiple locations.
4.8.4 Electromechanical components
Description
EMC-compliant installation includes overvoltage protection. Di󹪜erent components are suitable
depending on the type of voltage:
RC elements or varistors for AC-operated coils
Freewheeling diodes or varistors for DC-operated coils
The following components have overvoltage protection connected directly to the coil:
Coils of contactors
Relays
Solenoid valves
Motor holding brakes
Application planning
4.8EMC-compliant installation
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 93

Table of Contents