13.1.3.1 Restoring the drive data via the web server
Requirement
The converter is operated without an SD card.
You have a backup 󹪝le of the source converter on your operating unit.
In the description below, a distinction is made between restoring drive data from an
encrypted backup 󹪝le or from an unencrypted backup 󹪝le.
The rated power of the target converter is the same as the rated power of the converter from
which the backed-up data and settings originate.
Ideally, the target converter is in the factory setting.
It either involves a brand-new target converter or a target converter where all user-de󹪝ned
settings have been restored to the factory setting. You can 󹪝nd more information in Section
"Reset of all user-de󹪝ned settings to the factory setting via an SD card (Page587)".
Procedure
1. Switch o󹪜 the supply voltage of the source converter.
2. Release all of the connections at the source converter, replace the converter and re-establish
the connections at the target converter.
3. Switch on the supply voltage of the target converter.
4. Enter the IP address of the target converter, e.g. https://169.254.11.22, in the web browser.
The web server is started. The "Basic settings" page is displayed.
5. Make the basic settings for the converter.
You can 󹪝nd more information in Section "Basic settings (Page173)".
6. Click "Next".
The "Welcome to the Security Wizard" page is displayed.
7. Select the option "Exit the Security Wizard and continue with low security settings".
8. Call the "Backup and restore" menu.
9. Click the "Click to select 󹪝le, or drag and drop 󹪝le here" button to select the backup 󹪝le.
10.To restore the drive data, proceed as described below depending on the speci󹪝c application.
Corrective maintenance
13.1Service and maintenance for the converter
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 593

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals