EasyManua.ls Logo

Siemens SINAMICS SIMOTICS S200 PROFINET - Direct Setpoint Input (MDI)

Siemens SINAMICS SIMOTICS S200 PROFINET
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
are also e󹪜ective. Dynamic follo
wing error monitoring (p2546) in the position controller is
not e󹪜ective when traveling to the 󹪝xed stop. As long as the drive travels to the 󹪝xed stop or
is in 󹪝xed stop, the "Travel to 󹪝xed stop active" status bit r2683.14 is set.
6SHHGVHWSRLQW
$FWXDOWRUTXH
)L[HGVWRSUHDFKHG
0BOLPLW
7UDYHOWRIL[HGVWRSDFWLYH
7RUTXHOLPLWUHDFKHG
10.6.6 Direct setpoint input (MDI)
Overvie
w
The "direct setpoint input (MDI, Manual Data Input)" function allows for positioning (absolute,
relative) and setting-up (endless position-controlled) by means of direct setpoint inputs (e.g. via
the PLC using process data). A higher-level control provides the converter with the position
setpoint and traversing pro󹪝le.
Description of function
During traversing, the motion parameters can also be in󹪞uenced (on-the-󹪞y setpoint
acceptance) and an on-the-󹪞y change can be undertaken between the "setting-up" and
"positioning" modes. The "direct setpoint speci󹪝cation" mode (MDI) can also be used if the axis
is not homed in the "setting-up" or "relative positioning" modes.
"Setting-up" mode
The higher-level control selects the mode "Set-up":
Functions
10.6Basic positioner (EPOS)
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
390 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Related product manuals