10.5.7 Setting motor overload protection in accordance with UL 61800-5-1 Ed.2
Overvie
w
The motor overload protection function works without temperature sensors in the 1FL2 motors.
To comply with UL61800‑5‑1 Ed.2, you must make some additional settings when operating
the converter with a 1FL2 motor.
Requirement
You have completed quick commissioning with the correct motor data.
Procedure
Proceed as follows to activate the motor overload protection according to UL61800‑5‑1Ed.2:
1. Set p5375.0=1
2. Set p5375.1=1
Functions
10.5General functions
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 367