A01007 POWER ON for DRIVE-CLiQ component required
Message class: General drive fault (19)
Message value: Component number: %1
Component: None
Response: NONE
Acknowledgment: NONE
Explanation of the
mes
sage v
alue:
For %1
Component in target topology
Cause: A DRIVE-CLiQ component must be switched on again (POWER ON) (e.g. due to a rm
war
e update).
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Note:
For a component number = 1, a POWER ON of the Control Unit is required.
Remedy: - Switch o the pow
er supply of the specied DRIVE-CLiQ component and switch it on again.
- For SINUMERIK, auto commissioning is prevented. In this case, a POWER ON is required for all components and the auto
commissioning must be restarted.
A01009 Control Unit overtemperature
Message class: Overtemperature of the electronic components (6)
Message value: -
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
Cause: The temperature (r0037[0]) of the converter has exceeded the specied limit v
alue.
Remedy
: - Check the converter air intake.
- Check the con
verter fan.
Note:
The alarm is automatically withdrawn once the limit value has been fallen below.
F01011 Download interrupted
Message class: Error in the parameterization / conguration / commissioning procedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The project download was interrupted.
F
ault value (r0949, int
erpret decimal):
1: The user prematurely interrupted the project download.
2: The communication cable was interrupted (e.g. cable breakage, cable withdrawn).
3: The project download was prematurely exited by the commissioning tool.
100: Dierent versions between the rmware version and project les which were loaded by loading into the le system
"Download from memory card".
Note:
The response to an interrupted download is the state "rst commissioning".
Remedy: - Check the communication cable.
- Download the pr
oject again.
- Boot from previously saved les (switch-o/switch-on or p0976).
- When loading into the le system (download from memory card), use the matching version.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
438 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB