Component: Control Unit (CU)
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: At least one system overload has been identi󹪝ed.
F
ault value (r0949, int
erpret decimal):
1: Computing time load too high.
5: Peak load too high.
Note:
As long as this fault is present, it is not possible to save the parameters (p0977).
Remedy: - Reduce the computing time load of the drive unit to below 100 %.
- Deactivate functions.
- Deactiv
ate drive objects.
- Remove drive objects from the target topology.
- Note the DRIVE-CLiQ topology rules and if required, change the DRIVE-CLiQ topology.
F01068 CU: Data memory memory over󹪞o
w
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: Control Unit (CU)
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The utilization for a data memory area is too large.
F
ault value (r0949, int
erpret binary):
Bit 0 = 1: High-speed data memory 1 overloaded
Bit 1 = 1: High-speed data memory 2 overloaded
Bit 2 = 1: High-speed data memory 3 overloaded
Bit 3 = 1: High-speed data memory 4 overloaded
Remedy: - Deactivate function.
- Deactivate dr
ive object.
- Remove drive object from the target topology.
A01069 Parameter backup and device incompatible
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
Cause: The parameter backup on the memory card and the drive unit do not match.
The module boo
ts with t
he factory settings.
Example:
Devices A and B. are not compatible and a memory card with the parameter backup for device A is inserted in device B.
Remedy: - Insert a memory card with compatible parameter backup and carry out a POWER ON.
- Insert a memory car
d without parameter backup and carry out a POWER ON.
- Save the parameters (p0977 = 1).
F01070 Project/󹪝rmware is being downloaded to the memory card
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Message value: %1
Component: Control Unit (CU)
Response: OFF2
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
448 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals