Acknowledgment: IMMEDIATELY
Cause: Too many safety messages have occurred within a short time so that some have not been able to be displayed.
Remedy: No remedy required
F01800 Internal communications faulted
Message class: Internal (DRIVE-CLiQ) communication error (12)
Message value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause:
Remedy: Replace the component involved.
A01900 PN: Con󹪝guration teleg
ram error
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: A controller attempts to establish a connection using an incorrect con󹪝gur
ing teleg
ram.
Alarm value (r2124, interpret decimal):
2:
Too many PZD data words for output or input. The number of possible PZD is speci󹪝ed by the number of indices in r2050/
r2053.
3:
Uneven number of bytes for input or output.
4:
Setting data for synchronization not accepted. For more information, see A01902.
211:
Unknown parameterizing block.
Additional values:
Only for internal Siemens troubleshooting.
Remedy: Check the bus con󹪝guration on the contr
oller and device sides.
A01902 PN: Isochronous operation parameterization not permissible
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
486 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB