Cause: The power unit DC link was not able to be precharged within the expected time.
1) There is no line volt
age connected.
2) The line contactor/line side switch has not been closed.
3) The line voltage is too low.
4) Line voltage incorrectly set (p0210).
5) The precharging resistors are overheated as there were too many precharging operations per time unit.
6) The precharging resistors are overheated as the DC link capacitance is too high.
7) The precharging resistors are overheated because when there is no "ready for operation" (r0863.0) of the infeed unit,
power is taken from the DC link.
8) The precharging resistors are overheated as the line contactor was closed during the DC link fast discharge through the
Braking Module.
9) The DC link has either a ground fault or a short-circuit.
10) The precharging circuit is possibly defective (only for chassis units).
11) Infeed defective and/or fuse ruptured
Fault value (r0949, interpret binary):
yyyyxxxx hex:
yyyy = power unit state
0: Fault status (wait for OFF and fault acknowledgment).
1: Restart inhibit (wait for OFF).
2: Overvoltage condition detected -> change into the fault state.
3: Undervoltage condition detected -> change into the fault state.
4: Wait for bridging contactor to open -> change into the fault state.
5: Wait for bridging contactor to open -> change into restart inhibit.
6: Wait for bypass contactor to open
7: Commissioning.
8: Ready for precharging.
9: Precharging started, DC link voltage lower than the minimum switch-on voltage.
10: Precharging, DC link voltage end of precharging still not detected.
11: Wait for the end of the de-bounce time of the main contactor after precharging has been completed.
12: Precharging completed, ready for pulse enable.
13: It was detected that the STO terminal was energized at the power unit.
xxxx = Missing internal enable signals, power unit (inverted bit-coded, FFFF hex -> all internal enable signals available)
Bit 0: Power supply for the power semiconductor gating shut down.
Bit 1: Ground fault detected.
Bit 2: Peak current intervention.
Bit 3: I2t exceeded.
Bit 4. Thermal model overtemperature calculated.
Bit 5: (heat sink, gating module, power unit) overtemperature measured.
Bit 6: Reserved.
Bit 7: Overvoltage detected.
Bit 8: Power unit has completed precharging, ready for pulse enable.
Bit 9: STO terminal missing.
Bit 10: Overcurrent detected.
Bit 11: Armature short-circuit active.
Bit 12: DRIVE-CLiQ fault active.
Bit 13: Vce fault detected, transistor de-saturated due to overcurrent/short-circuit.
Bit 14: Undervoltage detected.
See also: p0210 (Device supply voltage)
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
548 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB