Remedy: - Check the fan involved.
- If requir
ed, replace the fan.
- For communication errors, update the software or replace the power unit.
Note:
If the alarm has been withdrawn, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched o the fan, and therefore can no longer evaluate the feedback signal.
F30050 Power unit: 24 V supply overvoltage
Message class: Supply voltage fault (overvoltage) (3)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: POWER ON
Cause: The voltage monitor signals an overvoltage fault on the module.
Remedy: - Check the 24 V power supply.
- Replace t
he module if necessar
y.
F30051 Power unit: Motor holding brake short-circuit detected
Message class: External measured value / signal state outside the permissible range (16)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: A short-circuit at the motor holding brake terminals has been detected.
F
ault value (r0949, int
erpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - Check the motor holding brake for a short-circuit.
- Check the connection and cable f
or the motor holding brake.
F30052 EEPROM data error
Message class: Hardware/software error (1)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: POWER ON
Cause: The EEPROM data of the power unit module are incorrect.
F
ault value (r0949, int
erpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: Replace the power unit module or update the EEPROM data.
F30053 FPGA data faulty
Message class: Hardware/software error (1)
Message value: %1
Component: Power Unit
Response: NONE
Acknowledgment: POWER ON
Cause: The FPGA data of the power unit are faulty. This can be caused, for example, if a rm
war
e update is interrupted.