EasyManua.ls Logo

Siemens SINAMICS SIMOTICS S200 PROFINET - Page 559

Siemens SINAMICS SIMOTICS S200 PROFINET
908 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Remedy: - Check the heat sink fan and replace if necessary.
- For communication err
ors, update the software or replace the power unit.
Note:
- If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched o󹪜 the fan, and therefore can no longer evaluate the feedback signal.
F30059 Power unit: Internal fan 1 defective
Message class: Auxiliary unit faulted (20)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The feedback signal of internal fan 1 signals a fault, or there is a communication error with the fan.
F
ault v
alue (r0949, int
erpret decimal):
0: Feedback signal of the fan signals a fault
1: Internal communication error to the fan
Remedy: - Check internal fan 1 and replace if necessary.
- For communication err
ors, update the software or replace the power unit.
Note:
If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched o󹪜 the fan, and therefore can no longer evaluate the feedback signal.
F30062 Bypass contactor opened under current
Message class: Infeed faulted (13)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The bypass contactor of the precharging unit has been opened under current.
P
ossible causes:
- A def
ect at the bypass contactor
Remedy: It is urgently recommended that the components involved are replaced to prevent serious damage to the entire converter
line-up.
F30068 Power unit: undertemperature inverter heat sink
Message class: Power electronics faulted (5)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The actual inverter heat sink temperature is below the permissible minimum value.
P
ossible causes:
- The po
wer unit is being operated at an ambient temperature that lies below the permissible range.
- The temperature sensor evaluation is defective.
Fault value (r0949, interpret decimal):
Inverter heat sink temperature [0.1 °C].
Remedy: - Ensure that higher ambient temperatures prevail.
- Replace the pow
er unit.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 557

Table of Contents

Related product manuals