Remedy: Check the following:
- Is the ambient tem
perature within the de󹪝ned limit values?
- Have the load conditions and the load duty cycle been appropriately dimensioned?
- Has the cooling failed?
A30251 Power unit: Recti󹪝er ov
ertemperature
Message class: Power electronics faulted (5)
Message value: -
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: The alarm threshold for the overtemperature of the r
ecti󹪝er has been reac
hed. The response is set using p0290.
If the temperature of the recti󹪝er increases by an additional 5 K, then fault F30037 is triggered.
Remedy: Check the following:
- Is the ambient tem
perature within the de󹪝ned limit values?
- Have the load conditions and the load duty cycle been appropriately dimensioned?
- Has the fan failed? Check the direction of rotation.
- Has a phase of the line supply failed?
- Is an arm of the supply (incoming) recti󹪝er defective?
A30252 Power unit: Chip overtemperature alarm
Message class: Power electronics faulted (5)
Message value: Power semiconductor: %1, temperature: [0.01 degrees C] %2
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: The chip temperature of the power semiconductor involved has exceeded the permissible alarm threshold.
No
te:
- If t
he chip temperature of the power semiconductor involved increases by 5K, then fault F30025 is initiated.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy= Power semiconductor, xxxx = Temperature in 0.01°C
Remedy: Check the following:
- Is the ambient tem
perature within the de󹪝ned limit values?
- Have the load conditions and the load duty cycle been appropriately dimensioned?
- Has the cooling failed?
- Pulse frequency too high?
A30253 Power unit: Overtemperature thermal model alarm
Message class: Power electronics faulted (5)
Message value: Power semiconductor: %1, temperature: [0.01 degrees C] %2
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: The temperature di󹪜er
ence betw
een the power semiconductor involved and the heat sink has exceeded the permissible
alarm threshold.
The maximum output current is reduced as overload response.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy= Power semiconductor, xxxx = Temperature in 0.01°C
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 561