A30259 Braking resistor value too low
Message class: Braking Module faulted (14)
Message value: %1
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: The braking resistor value used in p0216 is too low.
This can r
esult in an ex
cessively high braking current.
Alarm value (r2124, interpret decimal):
Minimum limit value of the braking resistor [0.1 Ohm]
See also: p0216 (Braking resistance value)
Remedy: - Use a braking resistor with the appropriate resistance value
- Observe t
he product documentation
F30260 Power unit: Fault in the driver supply for the power semiconductor
Message class: Hardware/software error (1)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: A fault has occurred in the driver supply of the power semiconductor.
Remedy: There is a hardware defect. The device must be replaced.
F30262 Power unit: Braking chopper defective
Message class: Power electronics faulted (5)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The braking chopper is defective.
Remedy: Replace the converter.
F30263 Power unit: Braking chopper upper defective
Message class: Power electronics faulted (5)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The upper braking chopper is defective.
Remedy: Replace the converter.
F30264 Power unit: Braking chopper inhibited due to implausible DC link voltage
Message class: Braking Module faulted (14)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY