Cause: Internal communications error. The nodes do not send and receive in synchronism.
Error cause:
33 (= 21 he
x):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - Carry out a POWER ON.
- Replace the component in
volved.
F30836 Power unit: Send error
Message class: Internal (DRIVE-CLiQ) communication error (12)
Message value: Component number: %1, fault cause: %2
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: Internal communications error. Data were not able to be sent.
Er
r
or cause:
65 (= 41 he
x):
Telegram type does not match send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: Carry out a POWER ON.
F30845 Power unit: Cyclic data transfer error
Message class: Internal (DRIVE-CLiQ) communication error (12)
Message value: Component number: %1, fault cause: %2
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: Internal communications error.
Er
ror cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: Carry out a POWER ON (switch-o󹪜/switch-on).
F30850 Power unit: Internal software error
Message class: Hardware/software error (1)
Message value: %1
Component: Power Unit
Response: OFF1
Acknowledgment: POWER ON
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
570 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Related product manuals