Cause: Internal communications error.
Error cause:
1 (= 01 he
x):
Checksum error (CRC error).
2 (= 02 hex):
Telegram is shorter than speci󹪝ed in the length byte or in the receive list.
3 (= 03 hex):
Telegram is longer than speci󹪝ed in the length byte or in the receive list.
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The internal communications from the component involved signals a failure of the supply voltage.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that speci󹪝ed in the length byte or in the receive list and the receive telegram is too early.
19 (= 13 hex):
The telegram is longer than that speci󹪝ed in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - Carry out a POWER ON (switch-o󹪜/switch-on).
- Chec
k the electrical cabinet design and cable routing for EMC compliance.
F30875 Power unit: power supply voltage failed
Message class: Supply voltage fault (undervoltage) (3)
Message value: Component number: %1, fault cause: %2
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The component involved has signaled that the 24 V supply has failed.
Er
r
or cause:
9 (= 09 he
x):
The power supply voltage for the components has failed.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
572 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB