In the following cases it may be necessary to reset all user-dened conv
erter settings to the
factory setting:
• The available credentials do not allow the necessary conguration of the converter (no
password for example).
• Before recommissioning of the converter, for example if the application use of the converter
changes.
• Before the converter is sold or disposed of, in order to erase all user-dened settings.
Requirement
• You can access the converter manually.
• All electrical connections from the converter to the motor are disconnected.
• The PROFINET connection to the control system and other devices is disconnected.
• You have an empty writable SD card with a maximum of 32 GB; e.g. 6SL5970-0AA00-0AA0.
Procedure
Proceed as follows to reset all user-dened converter settings to the factory setting:
1. Create an empty le called RESET.TXT in the root directory of the SD card.
2. Switch o the supply voltage to the converter.
3. Wait until all the LEDS on the converter have gone out.
4. Insert the SD card into the converter.
5. Switch on the supply voltage to the converter.
6. The converter deletes the user-dened settings.
7. The user-dened settings are deleted.
8. Remove the SD card.
Result
All user-dened converter settings are deleted.
The converter rmware is unchanged.
After the manual reset to factory settings, access to the web server is possible via the service
interface (X127) and via the PROFINET interface (X150). For access via the service interface
(X127), use the secure transmission protocol HTTPS.