Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
379
Table 3-12 Jumper setting for Nominal Current or Measuring Range
1)
Not for version with sensitive earth fault detection
Contacts of relays for binary outputs BO6, BO7 and BO8 can be configured as normally open or normally
closed (see also General Diagrams in the Appendix).
Table 3-13 Jumper setting for the Contact Type of the relays for BO6, BO7 and BO8
1)
Factory setting
The relays for binary outputs BO1 through BO5 can be connected to common potential, or configured individ-
ually for BO1, BO4 and BO5 (BO2 and BO3 are without function in this context) (see also General Diagrams
in the Appendix).
Table 3-14 Jumper settings for the configuration of the Common Potential of BO1 through BO5 or for con-
figuration of BO1, BO4 and BO5 as Single Relays
1)
Factory setting
Jumpers X71, X72 through X73 serve for setting the bus address. Their position may not be changed. The fol-
lowing table shows the preset jumper positions.
Table 3-15 Jumper settings of Bus address of the input/output board C-I/O-2
Jumper Nominal current 1 A
Measuring range 20 A
Nominal current 5 A
Measuring range 100 A
X51 1-2 1-2
X60 1-2 2-3
X61 2-5 3-5
X62 2-5 3-5
X63 2-5 3-5
X64
1)
2-5 3-5
For Jumper Open in quiescent state (NO)
1)
Closed in quiescent state (NC)
BO6 X41 1-2 2-3
BO7 X42 1-2 2-3
BO8 X43 1-2 2-3
Jumper BO1 through BO5 connected to
common potential
1)
BO1, BO4, BO5 configured as single relays (BO2, BO3
without function)
X80 1-2, 3-4 2-3, 4-5
X81 1-2, 3-4 2-3, 4-5
X82 2-3 1-2
Jumper Factory setting
X71 1-2 (H)
X72 1-2 (H)
X73 2-3 (L)