5-8
Pt. TYPE: SGENMON Description: Generator Monitor (Supervisory)
Circuit Status LCD Readout (2
nd
line) LED
Normal Generator Monitor NORMAL
Limited Generator Monitor SUPERVISORY S
Open Generator Monitor TROUBLE T
Short Generator Monitor SUPERVISORY S
Disable TBL Generator Monitor TROUBLE T
Class A TBL Generator Monitor TROUBLE T
Detailed Description: Same as GENMON except generator running will be
automatically displayed and require operator acknowledgement.
Figure 5-21. SGENMON Point Type
Pt. TYPE: FPUMP Description: Fire Pump Monitor
(No Supervisory)
Circuit Status LCD Readout (2
nd
line) LED
Normal Fire Pump Monitor OFF
Limited Fire Pump Monitor OFF
Open Fire Pump Monitor TROUBLE T
Short Fire Pump Monitor SUPERVISORY S
Disable TBL Fire Pump Monitor TROUBLE T
Class A TBL Fire Pump Monitor TROUBLE T
Detailed Description: Used to monitor Fire Pump conditions. The shorted
condition will indicate Fire Pump abnormal (if the <ö> key is pressed). A
current limited condition equals Fire Pump running (if the <ö> key is pressed).
Figure 5-22. FPUMP Point Type
Pt. TYPE: SFPUMP Description: Fire Pump Monitor (Supervisory)
Circuit Status LCD Readout (2
nd
line) LED
Normal Fire Pump Monitor NORMAL
Limited Fire Pump Monitor SUPERVISORY S
Open Fire Pump Monitor TROUBLE T
Short Fire Pump Monitor SUPERVISORY S
Disable TBL Fire Pump Monitor TROUBLE T
Class A TBL Fire Pump Monitor TROUBLE T
Detailed Description: Same as FPUMP except that fire pump running will
require operator acknowledgement.
Figure 5-23. SFPUMP Point Type
Continued on next page
Point Type Messages for Monitor Points, Continued
Monitor Points (continued)