CD600 Plus - User's Manual
4.16
TYPE MNEM DESCRIPTION RANGE DEFAULT
I CLMV Locks < > and < > keys
0 - No Lock
1 - When Input D has a high logic level
2 - When Input C has a high logic level
3 - When Inputs C or D have a high
logic level
0
I CLAM Locks <A/M> key
0 - No Lock
1 - When Input D has a high logic level
2 - When Input C has a high logic level
3 - When Inputs C or D have a high
logic level
0
I CHST
Restart condition - Operating mode after power
interruption
0 – Last
1 – Manual
2 - Auto
0
I CLIM Output limiter only on Automatic
0 - Manual and Auto
1 - Auto
0
I ASPD Actuation Speed in Manual 0.00-200.00%/s 10.00%/s
I ALOW Lower Limit -2.00 to +102.00% -2.00%
I AUPP Upper Limit -2.00 to +102.00% +102.00%
I ASLW Slew Rate for the Automatic mode 1.00 to 200.00%/s 200.00%/s
Number of Bytes per Type of Parameter: A = 8 C = 14 L = 8