EasyManua.ls Logo

SMAR CD600 Plus - Function 15 - Derivative; Lead-Lag (Ll); Operation

SMAR CD600 Plus
198 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CD600 Plus - User's Manual
4.40
Function 15 – Derivative / Lead-Lag (LL)
Operation
This is a dynamic compensation block that may operate with a derivative function as well as with a
lead-lag compensation function. Selection of either function is done with parameter
CDLL.
BLK 061/062
A
77/78
1 + T s
1 + T s
T
D
s
T
D
s
1+
This block reads inputs from -2 to 102% and provides output signals from -102 to +102%.
DERIVATIVE FUNCTION
While operating in the derivative mode, the block performs the following transfer function:
) (s I
Ts + 1
s
T
= ) (s O
D
Where,
O(s) and I(s) - are the Laplace transform of input and output functions, respectively.
T
D
- derivative constant, adjusted by parameter ATLE (min.)
T - lag constant, adjusted by parameter
ATLA (min.)
When
T=0, the output signal represents the input variation rate in the period determined by T
D
. For
example, if the input signal increases according to a slope of 15% per second and
TD=6 s (0.1
min.), the output signal will be 15. 6=90% while the slope lasts, returning to zero when there is a
constant input value.
When
T=0, the output signal is submitted to a lag. The response to a step function with amplitude A
is shown in Figure 4.15.1.
This function is used when the rate of change of a variable is desired.
INPUT
A
t
0
0
0
t
T
+T
tt
t
A
T
OUTPUT
Fig 4.15.1 - Response of Derivative Function with a Lag to an Input Step

Table of Contents

Other manuals for SMAR CD600 Plus