EasyManua.ls Logo

SMAR CD600 Plus - Page 51

SMAR CD600 Plus
198 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Library of Function Blocks
4.31
Integral action is transformed into a series of pulses of minimum width AWPL, with a frequency
determined by the integral time T
R
and by the control deviation.
For example, consider a case where the PID is adjusted with proportional gain equal to 1, with no
integral or derivative action; valve opening time = 1 minute and on instant t=0 there is a step error
equal to 25% (Figure 4.11.2).
25%
PID-OUT
75%
50%
STEP-OUT
“ON”
1
e
0
15
0
0
t(sec)
t(sec)
t(sec)
Proportional action
Fig 4.11.2 - Step Output for a 25% deviation with Proportional action only
In this example, 15 seconds of actuation are equivalent to 25% of the valve's excursion (0.25 min =
15 s).
The integral action works as a train of pulses with the same width. The total number of pulses in a
given interval of time depends on the integral action adjustment in the PID and on the individual
width of each pulse (AWPL).
Let's consider a case similar to the above example, where the PID has the integral action adjusted
to 1 minute/repetition and each pulse has a width of 3 seconds. As AWPL is expressed in number of
cycles and each cycle is 0.2 s, AWPL=3/0.2 = 15.
e
PID-OUT
STEP-OUT
25%
25%
“ON” 1
T (sec)
T (sec)
T (sec)
Integral
action only
3
0
060
333 3
Fig 4.11.3 - Step Output for a 25% deviation with Integral action only
The error is 25%. A standard I controller would increase/decrease the output by 25% in 1 minute
(T
R
).

Table of Contents

Other manuals for SMAR CD600 Plus