CD600 Plus - User's Manual
4.46
TYPE MNEM DESCRIPTION RANGE DEFAULT
I LIA Input A (Pressure or Specific Gravity) 0
I LIB Input B (Temperature) 0
I LIC Input C (Lower range flow rate) 0
I LID Input D (Upper range flow rate)
Addresses
0 to 170/225 to 240
0
I CTYP Type of compensation 0-Gas; 1-Liq.
2-Gas without;
3-Liq. without
0
R C-PO P
0
for Gas /T
c
for Liquid 0 to 10 E 37 1.0000
R C-AP
αp
0 to 10 E 37 0
R C-TO T
0
0 to 10 E 37 273.15
R C-AT
t
0 to 10 E 37 0
R C-CA Coefficient A -10 E 37 to 10 E 37 0
R C-CB Coefficient B -10 E 37 to 10 E 37 0
R C-CC Coefficient C -10 E 37 to 10 E 37 1.0000
R C-KK Constant K 0 to 10 E 37 273.15
P A-LL Maximum Low Flow 0.00% - 100.00% 0.00%
Number of Bytes per Type of Parameter: A = 2 C = 34 L = 8