EasyManua.ls Logo

SMAR CD600 Plus - Page 79

SMAR CD600 Plus
198 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Library of Function Blocks
4.59
Besides giving the corresponding high logic level output, the alarm status can also be shown on the
front panel display (see
SECTION 1 - ALARMS ACKNOWLEDGMENT). It can be configured
through the parameter
CFRT.
It is also possible to program an eight-characters alarm message, using the parameter
CMN1 (or
CMN2).
TYPE MNEM DESCRIPTION RANGE DEFAULT
I LIA Input A 0
I LIB Input B (Comparator Reference) 0
I LIC Input C 0
I LID Input D (Comparator Reference)
Addresses
0 to 170/225 to 240
0
I CTY1 First Comparator 0-Low/1-High/2-Equal 0
S CMN1 First Comparator Message ****** LOW COMP
I CTY2 Second Comparator 0-Low/1-High/2-Equal 1
S CMN2 2nd Comparator Message ****** HGH COMP
I
CFRT Indication on Front Panel
0 - None
1 - Indicates 1
2 - Indicates 2
3 - Indicates 1 and 2
4 - Indicates 1 with Auto Ack.
5 - Indicates 2 with Auto Ack.
6 - Indicates 1 and 2 with Auto Ack.
0
P ARG1 1st Comparator Limit -102.00% to +102.00% 0.00%
P ADB1 1st Comparator Hysteresis 0.00% to 100.00% 0.00%
P ARG2 2nd Comparator Limit -102.00% to +102.00% 100.0%
P ADB2 2nd Comparator Hysteresis 0.00% to 100.00% 0.00%
Number of Bytes per Type of Parameter: A = 8 C = 22 L = 8

Table of Contents

Other manuals for SMAR CD600 Plus