CD600 Plus - User's Manual
4.64
TYPE MNEM DESCRIPTION RANGE DEFAULT
I LIA Input A (Digital Interpretation) 0
I LIB Input B (Digital Interpretation) 0
I LIC Input C (Digital Interpretation)
Addresses
0 to 170 / 225 to 240
0
I CLOG
Defines the logic operation between
connected inputs
0 - OR 3 - NOR
1 - AND 4 - NAND
2 - XOR 5 - NXOR
0
I CNOT Inverts the input
0 - No inversion
1 - Inverts input A
2 - Inverts input B
3 - Inverts input A and B
4 - Inverts input C
5 - Inverts input A and C
6 - Inverts input B and C
7 - Inverts input A, B and C
0
Number of Bytes per Type of Parameter: A = 0 C = 4 L = 6