1
TimeHub 5500 TL1 Reference Manual
245
Troubleshooting
097-55501-02 Issue 5: June 2003
2
5
3
SSSSSSSSSSSS SSSS S SSSSS SSSSSSS S SSS S SSSSS
5
Sync in normal
operating mode*
SNOPER The indicated time constant is being
used by the clock card to track the
active input.
None required.
Tracking this
input*
SNTRCK The clock card has begun tracking
the indicated input.
None required.
Traffic value
invalid for card*
TRAOOR The value of the Traffic Data Pattern
(TRAFFIC) keyword is invalid for the
output driver card type.
Use the Edit Equipment command (ED-
EQPT) to set the TRAFFIC keyword value
to 255.
* This alarm can be set to other severities using the Edit Equipment (ED-EQPT) command.
Table M. Message Troubleshooting (cont’d)
Error Message/
Condition
Description Event Code Meaning Action

Table of Contents