5.FUNCTION SETTINGS
64
5-12. One-touch Tare Subtraction Reset
The subtracted Tare can be restored and Net weight becomes equal to Gross weight.
Operation
1) Press .
2) “ ” goes out.
- Tare subtraction reset by external signal
By short-circuiting A5pin (Tare subtraction OFF) and COM on the control connector, Tare
subtraction is immediately reset, and Net weight and Gross weight are equalized.
” goes out.
* If Net weight and Gross weight are not equalized by resetting Tare subtraction, the following
cause is presumable.
TARE
RESET
TARE
Cause Measure
The digital tare subtraction
function is valid.
Set the value of Tare Weight in setting mode
1 to 0, or set digital tare subtraction
ON/OFF in setting mode 2 to OFF.
TARE
OFF
ON
Pulse width 50msec or more