NOTE!
Only the standard I/O board statuses are available in the Monitor menu. You can
find the statuses of all the I/O board signals as raw data in the I/O and Hardware
menu.
Do a check of the statuses of the expander I/O board in the I/O and Hardware menu when the
system asks you to do it.
Table 21: Items in the monitoring menu
Index Monitoring value Unit Scale ID Description
V2.3.1 Output frequency Hz 0.01 1 The output frequency to motor
V2.3.2
Frequency
reference
Hz 0.01 25
The frequency reference to motor control
V2.3.3 Motor speed rpm 1 2 The actual speed of the motor in rpm
V2.3.4 Motor current A Varies 3
V2.3.5 Motor torque % 0.1 4 The calculated shaft torque
V2.3.7 Motor shaft power % 0.1 5
The calculated motor shaft power in
percentage
V2.3.8 Motor shaft power kW/hp Varies 73
The calculated motor shaft power in kW or
hp. The unit is set in the unit selection
parameter.
V2.3.9 Motor voltage V 0.1 6 The output voltage to motor
V2.3.10 DC link voltage V 1 7
The measured voltage in the DC-link of the
drive
V2.3.11 Unit temperature °C 0.1 8
The heatsink temperature in Celsius or
Fahrenheit
V2.3.12
Motor
temperature
% 0.1 9
The calculated motor temperature in
percentage of the nominal working
temperature
V2.3.13 Motor Preheat 1 1228
The status of the Motor preheat function
0 = OFF
1 = Heating (feeding DC-current)
V2.3.14 Torque reference % 0.1 18 The final torque reference to motor control
VACON · 102 MONITORING MENU