5.3 GROUP 3.3: REFERENCES
Table 38: Frequency reference parameters
Index Parameter Min Max Unit Default ID Description
P3.3.1.1
Minimum Frequency
Reference
0.00 P3.3.1.2. Hz 0.00 101
The minimum
frequency reference
P3.3.1.2
Maximum Frequency
Reference
P3.3.1.1. 320.00 Hz
50.00 /
60.00
102
The maximum
frequency reference
P3.3.1.3
Positive Frequency
Reference Limit
-320.0 320.0 Hz 320.00 1285
The final frequency
reference limit for the
positive direction.
P3.3.1.4
Negative Frequency
Reference Limit
-320.0 320.0 Hz -320.00 1286
The final frequency
reference limit for the
negative direction. Use
this parameter for
example to prevent the
motor from running in
the reverse direction.
P3.3.1.5
I/O Control
Reference A
Selection
0 19 5 * 117
Selection of the
reference source when
the control place is I/O
A.
0 = Preset Frequency 0
1 = Keypad reference
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor
potentiometer
8 = Joystick reference
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
The application that
you set with parameter
1.2 gives the default
value.
VACON · 124 PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205