4.1.9 EXTERNAL PID CONTROLLER MONITORING
Table 27: Monitoring of the values of the external PID controller
Index Monitoring value Unit Scale ID Description
V2.9.1 ExtPID setpoint Varies
As set in
P3.14.1.1
0 (See
5.14
Group
3.14:
External
PID
controller
)
83
The setpoint value of the external PID
controller in process units. You can use a
parameter to make the selection of the
process unit.
V2.9.2 ExtPID feedback Varies
As set in
P3.14.1.1
0
84
The feedback value of the external PID
controller in process units. You can use a
parameter to make the selection of the
process unit.
V2.9.3 ExtPID error value Varies
As set in
P3.14.1.1
0
85
The error value of the external PID
controller. It is the deviation of feedback from
the setpoint in process units. You can use a
parameter to make the selection of the
process unit.
V2.9.4 ExtPID output % 0.01 86
The external PID controller output as a
percentage (0..100%). It is possible to give
this value to, for example, the analogue
output.
V2.9.5 ExtPID status 1 87
0=Stopped
1=Running
2=In dead band (see 5.14 Group 3.14: External
PID controller)
4.1.10 MULTIPUMP MONITORING
Table 28: Multipump monitoring
Index Monitoring value Unit Scale ID Description
V2.10.1 Motors running 1 30
The number of motors that operate when the
Multi-pump function is used.
V2.10.2 Autochange 1 1113
The system tells you if an autochange is
necessary.
MONITORING MENU VACON · 109