4 To move the line to see the values of some other
location, use the arrow buttons Left and Right.
RUN
READY ALARM I/O
Motor Current
Motor Speed
0.01A
-254rpm
Table 20: The trend curve parameters
Index Parameter Min Max Unit Default ID Description
M2.2.1 View Trend curve
Go into this menu to
monitor values in a
curve form.
P2.2.2 Sampling interval 100 432000 ms 100 2368
Set the sampling
interval.
P2.2.3 Channel 1 min -214748 1000 -1000 2369
Used in scaling by
default. Adjustments
can be necessary.
P2.2.4 Channel 1 max -1000 214748 1000 2370
Used in scaling by
default. Adjustments
can be necessary.
P2.2.5 Channel 2 min -214748 1000 -1000 2371
Used in scaling by
default. Adjustments
can be necessary.
P2.2.6 Channel 2 max -1000 214748 1000 2372
Used in scaling by
default. Adjustments
can be necessary.
P2.2.7 Autoscale 0 1 0 2373
If the value of this
parameter is 1, the
signal is automatically
scaled between the
min and max values.
4.1.3 BASIC
You can see the basic monitoring values and their related data in the next table.
MONITORING MENU VACON · 101