P3.20.8 (P3.5.1.44) BRAKE FEEDBACK (ID 1210)
This parameter includes the digital input selection for the status signal of the mechanical
brake. The Brake feedback signal is used if the value for parameter P3.20.1 is Enabled with
brake status supervision.
Connect this digital input signal to an auxiliary contact of the mechanical brake.
The contact is open = the mechanical brake is closed
The contact is closed = the mechanical brake is open
If the brake opening command is given, but the contact of the brake feedback signal does not
close in given time, a mechanical brake fault shows (fault code 58).
9.18 PUMP CONTROL
9.18.1 AUTO-CLEANING
Use the Auto-cleaning function to remove dirt or other material from the pump impeller. You
can also use the function to clear a blocked pipe or valve. You can use the auto-cleaning, for
example, in wastewater systems to keep the performance of the pump satisfactory.
P3.21.1.1 CLEANING FUNCTION (ID 1714)
If you enable the parameter Cleaning Function, the auto-cleaning starts, and activates the
digital input signal in parameter P3.21.1.2.
P3.21.1.2 CLEANING ACTIVATION (ID 1715)
P3.21.1.3 CLEANING CYCLES (ID 1716)
The parameter Cleaning Cycles tells how many times the forward or the reverse cleaning
cycle is done.
P3.21.1.4 CLEAN FORWARD FREQUENCY (ID 1717)
The Auto-cleaning function accelerates and decelerates the pump to remove the dirt.
You can set the frequency and time of the cleaning cycle with the parameters P3.21.1.4,
P3.21.1.5, P3.21.1.6 and P3.21.1.7.
P3.21.1.5 CLEAN FORWARD TIME (ID 1718)
See parameter P3.21.1.4 Clean Forward Frequency.
P3.21.1.6 CLEAN REVERSE FREQUENCY (ID 1719)
See parameter P3.21.1.4 Clean Forward Frequency.
P3.21.1.7 CLEAN REVERSE TIME (ID 1720)
See parameter P3.21.1.4 Clean Forward Frequency.
PARAMETER DESCRIPTIONS VACON · 311