12
P1.26 Analogue Input 2 Signal Range
0=0…10V / 0…20mA
1=2…10V / 4…20mA
13
Set Local Control Place (where the drive start/stop
commands and the frequency reference is given
when Local control is active)
Fieldbus
Keypad
I/O (B) terminal
If you set I/O (B) Terminal as the value for Local Control Place, you see the next question. With
other selections, the wizard goes directly to question 16.
14
P1.25 Analogue Input 1 Signal Range
0=0…10V / 0…20mA
1=2…10V / 4…20mA
The Local/Remote application wizard is completed.
2.3 MULTI-STEP SPEED APPLICATION WIZARD
The application wizard helps you to set the basic parameters that are related to the
application.
To start the Multi-step speed application wizard, set the value Multi-step speed to parameter
P1.2 Application (ID 212) in the keypad.
NOTE!
If you start the application wizard from the Start-up wizard, the wizard shows only
the I/O configuration.
1
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate of the motor)
PM motor
Induction motor
2
Set a value for P3.1.1.1 Motor Nominal Voltage (so
that it agrees with the nameplate of the motor)
Range: Varies
3
Set a value for P3.1.1.2 Motor Nominal Frequency
(so that it agrees with the nameplate of the motor)
Range: 8.00…320.00 Hz
4
Set a value for P3.1.1.3 Motor Nominal Speed (so
that it agrees with the nameplate of the motor)
Range: 24…19200 rpm
5
Set a value for P3.1.1.4 Motor Nominal Current (so
that it agrees with the nameplate of the motor)
Range: Varies
If you set Motor Type to Induction Motor, you see the next question. If your selection is PM
Motor, the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard goes
directly to question 7.
WIZARDS VACON · 65
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
2