5.14 GROUP 3.14: EXTERNAL PID CONTROLLER
Table 92: Basic settings for the external PID controller
Index Parameter Min Max Unit Default ID Description
P3.14.1.1 Enable External PID 0 1 0 1630
0 = Disabled
1 = Enabled
P3.14.1.2 Start Signal
DigIN
Slot0.2
1049
FALSE = PID2 in stop
mode
TRUE = PID2
regulating
If the PID2 controller is
not enabled in the
Basic menu for PID2,
this parameter has no
effect.
P3.14.1.3 Output in Stop 0.0 100.0 % 0.0 1100
The output value of the
PID controller as a
percentage of its
maximum output value
when it is stopped from
a digital output.
P3.14.1.4 PID Gain 0.00 1000.00 % 100.00 1631
P3.14.1.5 PID Integration Time 0.00 600.00 s 1.00 1632
P3.14.1.6 PID Derivation Time 0.00 100.00 s 0.00 1633
P3.14.1.7
Process Unit
Selection
0 37 0 1635
P3.14.1.8 Process Unit Min Varies Varies Varies 0 1664
P3.14.1.9 Process Unit Max Varies Varies Varies 100 1665
P3.14.1.10
Process Unit
Decimals
0 4 2 1666
P3.14.1.11 Error Inversion 0 1 0 1636
P3.14.1.12 Dead Band Varies Varies Varies 0.0 1637
P3.14.1.13 Dead Band Delay 0.00 320.00 s 0.00 1638
VACON · 188 PARAMETERS MENU