Table 91: Frost protection parameters
Index Parameter Min Max Unit Default ID Description
P3.13.10.4
Temperature Signal
Maximum
P3.13.10
.3
300.0 °C/°F 200.0 (°C) 1707
The temperature value
that agrees to the
maximum value of the
set temperature signal.
P3.13.10.5
Frost Protection
Temperature
P3.13.10
.3
P3.13.10.
4
°C/°F 5.00 1708
The temperature limit
below which the Frost
protection function
activates.
P3.13.10.6
Frost Protection
Frequency
0.0 Varies Hz 10.0 1710
The constant frequency
reference that is used
when the Frost
protection function
activates.
V3.13.10.7
Frost Temperature
Monitoring
Varies Varies °C/°F 1711
The monitoring value
for the measured
temperature signal in
the Frost protection
function. Scaling value:
0.1.
PARAMETERS MENU VACON · 187