EasyManuals Logo

Vacon 100 Applications Manual

Vacon 100
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #201 background imageLoading...
Page #201 background image
5.20 GROUP 3.21: PUMP CONTROL
Table 102: Auto-cleaning parameters
Index Parameter Min Max Unit Default ID Description
P3.21.1.1
Cleaning Function 0 1 0 1714
0 = Disabled
1 = Enabled
P3.21.1.2
Cleaning Activation
DigIN
Slot0.1
1715
The digital input signal
that starts the Auto-
cleaning sequence. The
auto-cleaning stops if
the activation signal is
removed before the
sequence is complete.
NOTE!
If the input is
activated, the drive
starts.
P3.21.1.3
Cleaning Cycles 1 100 5 1716
The quantity of forward
or reverse cleaning
cycles.
P3.21.1.4
Clean Forward
Frequency
0.00 50.00 Hz 45.00 1717
The forward direction
frequency in the Auto-
cleaning cycle.
P3.21.1.5
Clean Forward Time 0.00 320.00 s 2.00 1718
The operation time for
the forward direction
frequency in the Auto-
cleaning cycle.
P3.21.1.6
Clean Reverse
Frequency
0.00 50.00 Hz 45.00 1719
The reverse direction
frequency in the Auto-
cleaning cycle.
P3.21.1.7
Clean Reverse Time 0.00 320.00 s 0.00 1720
The operation time for
reverse direction
frequency in the Auto-
cleaning cycle.
P3.21.1.8
Cleaning
Acceleration Time
0.1 300.0 s 0.1 1721
The motor acceleration
time when the Auto-
cleaning is active.
PARAMETERS MENU VACON · 201
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
5

Table of Contents

Other manuals for Vacon 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 and is the answer not in the manual?

Vacon 100 Specifications

General IconGeneral
Product typeAC Drive
Enclosure classIP20
EMC filterBuilt-in
Power0.25 kW - 5.5 kW
Cooling methodFan
Braking chopperOptional

Related product manuals