5.20 GROUP 3.21: PUMP CONTROL
Table 102: Auto-cleaning parameters
Index Parameter Min Max Unit Default ID Description
P3.21.1.1
Cleaning Function 0 1 0 1714
0 = Disabled
1 = Enabled
P3.21.1.2
Cleaning Activation
DigIN
Slot0.1
1715
The digital input signal
that starts the Auto-
cleaning sequence. The
auto-cleaning stops if
the activation signal is
removed before the
sequence is complete.
NOTE!
If the input is
activated, the drive
starts.
P3.21.1.3
Cleaning Cycles 1 100 5 1716
The quantity of forward
or reverse cleaning
cycles.
P3.21.1.4
Clean Forward
Frequency
0.00 50.00 Hz 45.00 1717
The forward direction
frequency in the Auto-
cleaning cycle.
P3.21.1.5
Clean Forward Time 0.00 320.00 s 2.00 1718
The operation time for
the forward direction
frequency in the Auto-
cleaning cycle.
P3.21.1.6
Clean Reverse
Frequency
0.00 50.00 Hz 45.00 1719
The reverse direction
frequency in the Auto-
cleaning cycle.
P3.21.1.7
Clean Reverse Time 0.00 320.00 s 0.00 1720
The operation time for
reverse direction
frequency in the Auto-
cleaning cycle.
P3.21.1.8
Cleaning
Acceleration Time
0.1 300.0 s 0.1 1721
The motor acceleration
time when the Auto-
cleaning is active.
PARAMETERS MENU VACON · 201