9.10 AUTOMATIC RESET
P3.10.1 AUTOMATIC RESET (ID 731)
Use parameter P3.10.1 to enable the Automatic reset function. To make a selection of faults
that are reset automatically, give the value 0 or 1 to parameters from P3.10.6 to P3.10.13.
NOTE!
The automatic reset function is available only for some fault types.
P3.10.3 WAIT TIME (ID 717)
P3.10.4 TRIAL TIME (ID 718)
Use this parameter to set the trial time for the automatic reset function. During the trial
time, the automatic reset function tries to reset the faults that occur. The time count starts
from the first automatic reset. The next fault starts the trial time count again.
P3.10.5 NUMBER OF TRIALS (ID 759)
If the number of trials during the trial time is more than the value of this parameter, a
permanent fault shows. If not, the fault goes out of view after the trial time is completed.
With parameter P3.10.5, you can set the maximum number of automatic reset trials during
the trial time set in P3.10.4. The fault type does not have an effect on the maximum number.
PARAMETER DESCRIPTIONS VACON · 285