5.10 GROUP 3.10: AUTOMATIC RESET
Table 72: Autoreset settings
Index Parameter Min Max Unit Default ID Description
P3.10.1
Automatic Reset 0 1 0 731
0 = Disabled
1 = Enabled
P3.10.2 Restart Function 0 1 1 719
The selection of the
start mode for
Automatic reset.
0 = Flying start
1 = According to
P3.2.4.
P3.10.3
Wait Time 0.10
10000.0
0
s 0.50 717
The wait time before
the first reset is done.
P3.10.4
Trial Time 0.00
10000.0
0
s 60.00 718
When the trial time is
over, and the fault is
still active, the drive
will trip.
P3.10.5
Number of Trials 1 10 4 759
The total quantity of
trials. The fault type
does not have an effect
on it. If the drive is not
able to be reset with
the quantity of trials
and the set trial time, a
fault shows.
P3.10.6
Autoreset:
Undervoltage
0 1 1 720
Autoreset permitted?
0 = No
1 = Yes
P3.10.7
Autoreset:
Overvoltage
0 1 1 721
Autoreset permitted?
0 = No
1 = Yes
P3.10.8
Autoreset:
Overcurrent
0 1 1 722
Autoreset permitted?
0 = No
1 = Yes