9.7.5 DIGITAL OUTPUTS
P3.5.3.2.1 BASIC RO1 FUNCTION (ID 11001)
Table 120: The output signals through RO1
Selection
number
Selection name Description
0 Not used The output is not used.
1 Ready The AC drive is ready to operate.
2 Run The AC drive operates (the motor runs).
3 General fault A fault trip occurred.
4 General fault inverted A fault trip did not occur.
5 General alarm An alarm occurred.
6 Reversed The reverse command is given.
7
At speed The output frequency has become the same as the set
frequency reference.
8 Thermistor fault A thermistor fault occurred.
9
Motor regulator activated One of the limit regulators (for example current limit or
torque limit) is activated.
10 Start signal active The start command of the drive is active.
11
Keypad control active The selection is keypad control (the active control place is
keypad).
12
I/O control B active The selection is I/O control place B (the active control place
is I/O B).
13 Limit supervision 1 The limit supervision activates if the signal value goes below
or above the set supervision limit (P3.8.3 or P3.8.7).
14 Limit supervision 2
15 Fire mode active The Fire mode function is active.
16 Jogging active The Jogging function is active.
17
Preset Frequency active The selection of preset frequency was made with digital input
signals.
18 Quick Stop active The Quick stop function is activated.
19 PID in Sleep mode The PID controller is in the sleep mode.
20 PID Soft Fill activated The Soft fill function of the PID controller is activated.
21
PID feedback supervision The feedback value of the PID controller is not in the
supervision limits.
PARAMETER DESCRIPTIONS VACON · 269