5.5 GROUP 3.5: I/O CONFIGURATION
Table 50: Digital input settings
Index Parameter Default ID Description
P3.5.1.1 Control Signal 1 A DigIN SlotA.1 * 403
Ctrl signal 1 when the control place is
I/O A (FWD).
P3.5.1.2 Control Signal 2 A DigIN SlotA.2 * 404
Ctrl signal 2 when the control place is
I/O A (REV).
P3.5.1.3 Control Signal 3 A DigIN Slot0.1 434
Ctrl signal 3 when the control place is
I/O A.
P3.5.1.4 Control Signal 1 B DigIN Slot0.1 * 423
Start signal 1 when the control place
is I/O B.
P3.5.1.5 Control Signal 2 B DigIN Slot0.1 * 424
Start signal 2 when the control place
is I/O B.
P3.5.1.6 Control Signal 3 B DigIN Slot0.1 435
Start signal 3 when the control place
is I/O B.
P3.5.1.7 I/O B Control Force DigIN Slot0.1 * 425
TRUE = Force the control place to I/O
B.
P3.5.1.8 I/O B Reference Force DigIN Slot0.1 * 343
TRUE = I/O reference B (P3.3.1.6)
gives the frequency reference.
P3.5.1.9 Fieldbus Control Force DigIN Slot0.1 * 411 Force the control to fieldbus.
P3.5.1.10 Keypad Control Force DigIN Slot0.1 * 410 Force the control to keypad.
P3.5.1.11 External Fault Close DigIN SlotA.3 * 405
FALSE = OK
TRUE = External fault
P3.5.1.12 External Fault Open DigIN Slot0.2 406
FALSE = External fault
TRUE = OK
P3.5.1.13 Fault Reset Close DigIN SlotA.6 * 414 TRUE = Resets all active faults.
P3.5.1.14 Fault Reset Open DigIN Slot0.1 213 FALSE = Resets all active faults.
P3.5.1.15 Run Enable DigIN Slot0.2 407
You can set the drive in Ready state,
when this is ON.
P3.5.1.16
Run Interlock 1 DigIN Slot0.2 1041
The drive can be ready, but the start
is not possible when the interlock is
on (Damper interlock).
PARAMETERS MENU VACON · 137