Table 50: Digital input settings
Index Parameter Default ID Description
P3.5.1.17
Run Interlock 2 DigIN Slot0.2 1042
As above.
P3.5.1.18 Motor Preheat ON DigIN Slot0.1 1044
FALSE = No action.
TRUE = Uses the DC current of the
motor preheat in Stop state. Used
when the value of P3.18.1 is 2.
P3.5.1.19 Ramp 2 Selection DigIN Slot0.1 * 408
Switch between ramps 1 and 2.
FALSE = Ramp 1 Shape, Acceleration
Time 1 and Deceleration Time 1.
TRUE = Ramp 2 Shape, Acceleration
Time 2 and Deceleration Time 2.
P3.5.1.20 Acc/Dec Prohibit DigIN Slot0.1 415
No acceleration or deceleration is
possible until the contact is open.
P3.5.1.21 Preset Frequency Selection 0 DigIN SlotA.4 * 419
A binary selector for preset speeds
(0-7). See Table 41 Preset frequency
parameters.
P3.5.1.22 Preset Frequency Selection 1 DigIN SlotA.5 * 420
A binary selector for preset speeds
(0-7). See Table 41 Preset frequency
parameters.
P3.5.1.23 Preset Frequency Selection 2 DigIN Slot0.1 * 421
A binary selector for preset speeds
(0-7). See Table 41 Preset frequency
parameters.
P3.5.1.24 Motor Potentiometer UP DigIN Slot0.1 * 418
FALSE = Not active
TRUE = Active. The motor
potentiometer reference INCREASES
until the contact is open.
P3.5.1.25 Motor Potentiometer DOWN DigIN Slot0.1 * 417
FALSE = Not active
TRUE = Active. The motor
potentiometer reference
DECREASES until the contact is
open.
P3.5.1.26 Quick Stop Activation DigIN Slot0.2 1213
FALSE = Activated
To configure these functions, see
Table 67 Quick stop settings.
VACON · 138 PARAMETERS MENU