Table 41: Preset frequency parameters
Index Parameter Min Max Unit Default ID Description
P3.3.3.1
Preset Frequency
Mode
0 1 0 * 182
0 = Binary coded
1 = Number of inputs
The number of preset
speed digital inputs
that are active define
the preset frequency.
P3.3.3.2
Preset Frequency 0 P3.3.1.1 P3.3.1.2 Hz 5.00 180
The basic preset
frequency 0 when it is
set with P3.3.1.5.
P3.3.3.3
Preset Frequency 1 P3.3.1.1 P3.3.1.2 Hz 10.00 * 105
Make the selection
with digital input
Preset frequency
selection 0 (P3.3.3.10).
P3.3.3.4
Preset Frequency 2 P3.3.1.1 P3.3.1.2 Hz 15.00 * 106
Make the selection
with digital input
Preset frequency
selection 1 (P3.3.3.11).
P3.3.3.5
Preset Frequency 3 P3.3.1.1 P3.3.1.2 Hz 20.00 * 126
Make the selection
with digital inputs
Preset frequency
selection 0 & 1.
P3.3.3.6
Preset Frequency 4 P3.3.1.1 P3.3.1.2 Hz 25.00 * 127
Make the selection
with digital input
Preset frequency
selection 2 (P3.3.3.12).
P3.3.3.7
Preset Frequency 5 P3.3.1.1 P3.3.1.2 Hz 30.00 * 128
Make the selection
with digital inputs
Preset frequency
selection 0 & 2.
P3.3.3.8
Preset Frequency 6 P3.3.1.1 P3.3.1.2 Hz 40.00 * 129
Make the selection
with digital inputs
Preset frequency
selection 1 & 2.
P3.3.3.9
Preset Frequency 7 P3.3.1.1 P3.3.1.2 Hz 50.00 * 130
Make the selection
with digital inputs
Preset frequency
selection 0 & 1 & 2.
P3.3.3.10
Preset Frequency
Selection 0
DigIN
SlotA.4
419
A binary selector for
Preset speeds (0-7).
See parameters
P3.3.3.2 to P3.3.3.9.
VACON · 130 PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205