5.9 GROUP 3.9: PROTECTIONS
Table 63: General protections settings
Index Parameter Min Max Unit Default ID Description
P3.9.1.2
Response to External
Fault
0 3 2 701
0 = No action
1 = Alarm
2 = Fault (Stop
according to stop
function)
3 = Fault (Stop by
coasting)
P3.9.1.3 Input Phase Fault 0 1 0 730
0 = 3-phase support
1 = 1-phase support
If you use the 1-phase
supply, the value must
be 1-phase support.
P3.9.1.4 Undervoltage Fault 0 1 0 727
0 = Fault stored in
history
1 = Fault not stored in
history
P3.9.1.5
Response to Output
Phase Fault
0 3 2 702
See P3.9.1.2.
P3.9.1.6
Response to
Fieldbus
Communication
Fault
0 5 3 733
0 = No action
1 = Alarm
2 = Alarm + preset
fault frequency
(P3.9.1.12)
3 = Fault (Stop
according to stop
function)
4 = Fault (Stop by
coasting
P3.9.1.7
Slot Communication
Fault
0 3 2 734
See P3.9.1.2.
P3.9.1.8 Thermistor Fault 0 3 0 732 See P3.9.1.2.
P3.9.1.9 PID Soft Fill Fault 0 3 2 748 See P3.9.1.2.
P3.9.1.10
Response to PID
Supervision Fault
0 3 2 749
See P3.9.1.2.
P3.9.1.11
Response to External
PID Supervision
Fault
0 3 2 757
See P3.9.1.2.
PARAMETERS MENU VACON · 155