5.17 GROUP 3.17: FIRE MODE
Table 99: Fire mode parameters
Index Parameter Min Max Unit Default ID Description
P3.17.1
Fire Mode Password 0 9999 0 1599
1002 = Enabled
1234 = Test mode
P3.17.2
Fire Mode Frequency
Source
0 18 0 1617
Selection of the
frequency reference
source when Fire mode
is active. This enables
the selection of for
example the AI1 or the
PID controller as the
reference source when
you operate Fire Mode.
0 = Fire Mode
frequency
1 = Preset speeds
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1
8 = Motor
potentiometer
9 = Block Out.1
10 = Block Out.2
11 = Block Out.3
12 = Block Out.4
13 = Block Out.5
14 = Block Out.6
15 = Block Out.7
16 = Block Out.8
17 = Block Out.9
18 = Block Out.10
P3.17.3
Fire Mode Frequency 8.00 P3.3.1.2 Hz 50.00 1598
The frequency that is
used when Fire mode
is active.
P3.17.4
Fire Mode Activation
on OPEN
DigIN
Slot0.2
1596
FALSE = Fire Mode
active
TRUE = No action
P3.17.5
Fire Mode Activation
on CLOSE
DigIN
Slot0.1
1619
FALSE = No action
TRUE = Fire Mode
active