Set a value for P3.15.3 Include FC
0 = Disabled
1 = Enabled
19 Set a value for P3.15.5 Autochange Interval 0.0...3000.0 h
20 Set a value for P3.15.6 Autochange: Frequency Limit 0.00...50.00 Hz
21 Set a value for P3.15.8 Bandwidth 0...100%
22 Set a value for P3.15.9 Bandwidth Delay 0...3600 s
After this, the display will show the digital input and relay output configuration that the
application does automatically. Write these values down. This function is not available in the
text display.
2.8 FIRE MODE WIZARD
To start the Fire Mode Wizard, make the selection Activate for parameter B1.1.4 in the Quick
setup menu.
CAUTION!
Before you continue, read about the password and warranty in Chapter 9.15 Fire
mode.
1
Set a value for parameter P3.17.2 Fire Mode
Frequency Source
More than 1 selection
If you set a value other than Fire mode frequency, the wizard goes directly to question 3.