Set a value for parameter P3.17.3 Fire Mode
Frequency
8.00 Hz...P3.3.1.2 (MaxFreqRef)
3
Activate the signal when the contact opens or when
it closes
0 = Open contact
1 = Closed contact
4
Set a value for parameters P3.17.4 Fire Mode
Activation on OPEN / P3.17.5 Fire Mode Activation
on CLOSE
Make a selection of a digital input to activate
Fire mode. See also Chapter 9.7.1
Programming of digital and analogue inputs.
5
Set a value for parameter P3.17.6 Fire Mode
Reverse
Make a selection of a digital input to activate
the reverse direction in Fire mode.
DigIn Slot0.1 = FORWARD
DigIn Slot0.2 = REVERSE
6
Set a value for P3.17.1 Fire Mode Password Set a password to enable the Fire mode
function.
1234 = Enable test mode
1002 = Enable Fire mode
WIZARDS VACON · 73