The Standard application wizard is completed.
2.2 LOCAL/REMOTE APPLICATION WIZARD
The application wizard helps you to set the application related basic parameters.
To start the Local/Remote application wizard, set the value Local/Remote to parameter P1.2
Application (ID 212) in the keypad.
NOTE!
If you start the application wizard from the Start-up wizard, the wizard goes directly
to question 11.
1
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate of the motor)
PM motor
Induction motor
2
Set a value for P3.1.1.1 Motor Nominal Voltage (so
that it agrees with the nameplate of the motor)
Range: Varies
3
Set a value for P3.1.1.2 Motor Nominal Frequency
(so that it agrees with the nameplate of the motor)
Range: 8.00...320.00 Hz
4
Set a value for P3.1.1.3 Motor Nominal Speed (so
that it agrees with the nameplate of the motor)
Range: 24...19200 rpm
5
Set a value for P3.1.1.4 Motor Nominal Current (so
that it agrees with the nameplate of the motor)
Range: Varies
If you set Motor Type to Induction Motor, you see the next question. If your selection is PM
Motor, the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard goes
directly to question 7.
6
Set a value for P3.1.1.5 Motor Cos Phi (so that it
agrees with the nameplate of the motor)
Range: 0.30…1.00
7
Set a value for P3.3.1.1 Minimum Frequency
Reference
Range: 0.00…P3.3.1.2 Hz
8
Set a value for P3.3.1.2 Maximum Frequency
Reference
Range: P3.3.1.1…320.00 Hz
9 Set a value for P3.4.1.2 Acceleration Time 1 Range: 0.1…300.0 s
10 Set a value for P3.4.1.3 Deceleration Time 1 Range: 0.1…300.0 s
11
Make a selection of the Remote control place
(where you give the start and stop commands, and
the frequency reference of the drive when Remote
control is active)
I/O terminal
Fieldbus
If you set I/O Terminal as the value for Remote Control Place, you see the next question. If you
set Fieldbus, the wizard goes directly to question 14.