EasyManua.ls Logo

Vacon 100 - CONTROL BITS MAPPING; MAPPING OF VACON DATA ONTO STANDARD INPUT ASSEMBLIES

Vacon 100
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 WIZARDS
2.1 STANDARD APPLICATION WIZARD
The application wizard helps you to set the basic parameters that are related to the
application.
To start the Standard application wizard, set the value Standard to parameter P1.2
Application (ID 212) in the keypad.
NOTE!
If you start the application wizard from the Start-up wizard, the wizard goes directly
to question 11.
1
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate of the motor)
PM motor
Induction motor
2
Set a value for P3.1.1.1 Motor Nominal Voltage (so
that it agrees with the nameplate of the motor)
Range: Varies
3
Set a value for P3.1.1.2 Motor Nominal Frequency
(so that it agrees with the nameplate of the motor)
Range: 8.00...320.00 Hz
4
Set a value for P3.1.1.3 Motor Nominal Speed (so
that it agrees with the nameplate of the motor)
Range: 24...19200 rpm
5
Set a value for P3.1.1.4 Motor Nominal Current (so
that it agrees with the nameplate of the motor)
Range: Varies
If you set Motor Type to Induction Motor, you see the next question. If your selection is PM
Motor, the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard goes
directly to question 7.
6
Set a value for P3.3.1.5 Motor Cos Phi (so that it
agrees with the nameplate of the motor)
Range: 0.3...1.00
7
Set a value for P3.3.1.1 Minimum Frequency
Reference
Range: 0.00...P3.3.1.2 Hz
8
Set a value for P3.3.1.1 Maximum Frequency
Reference
Range: P3.3.1.1...320.00 Hz
9 Set a value for P3.4.1.2 Acceleration Time 1 Range: 0.1...300.0 s
10 Set a value for P3.4.1.2 Deceleration Time 1 Range: 0.1...300.0 s
11
Make a selection of a control place (where you give
the start and stop commands, and the frequency
reference of the drive)
I/O terminal
Fieldbus
Keypad
WIZARDS VACON · 63