5.15 GROUP 3.15: MULTIPUMP
Table 96: Multipump parameters
Index Parameter Min Max Unit Default ID Description
P3.15.1 Number of Motors 1 6 1 1001
The quantity of motors
(or pumps or fans) that
there are in the
multipump system.
P3.15.2
Interlock Function 0 1 1 1032
Enable or disable the
interlocks. You can use
the interlocks to tell
the system if a motor is
connected.
0 = Disabled
1 = Enabled
P3.15.3
Include FC 0 1 1 1028
Include the AC drive in
the autochange and
interlock system.
0 = Disabled
1 = Enabled
P3.15.4
Autochange 0 1 1 1027
Enable or disable the
rotation of the start
sequence and the
priority of motors.
0 = Disabled
1 = Enabled
P3.15.5 Autochange Interval 0.0 3000.0 h 48.0 1029
When this time is over,
the autochange occurs
if the capacity is below
the level set with
P3.15.6. and P3.15.7.
P3.15.6
Autochange:
Frequency Limit
0.00 P3.3.1.2 Hz 25.00 1031
These parameters
define the level below
which the capacity
must stay for the
autochange to occur.
P3.15.7
Autochange: Motor
Limit
1 6 1 1030
PARAMETERS MENU VACON · 193