6
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
See table Analogue inputs in Chapter 5.5
Group 3.5: I/O configuration.
7
Set a value for P3.13.1.8 Error Inversion
0 = Normal
1 = Inverted
8
Set a value for P3.13.2.6 Setpoint Source 1 Selection See table Setpoints in Chapter 5.13 Group
3.13: PID controller.
If you make a selection of an analogue input signal, you see the question 9. With other
selections, the wizard goes to question 11.
If you set Keypad Setpoint 1 or Keypad Setpoint 2 for the value, you see the question 10.
9
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
See table Analogue inputs in Chapter 5.5
Group 3.5: I/O configuration.
10
Set a value for P3.13.2.1 (Keypad setpoint 1) and
P3.13.2.2 (Keypad setpoint 2)
Varies
11
Using the sleep function
No
Yes
If you give the value Yes for the question 11, you see the next 3 questions.
12
Set a value for P3.13.5.1 Sleep Frequency Limit 1 0.00...320.00 Hz
13 Set a value for P3.13.5.2 Sleep Delay 1 0...3000 s
14 Set a value for P3.13.5.6 Wake-up Level 1 The range depends on the set process unit.
15 Set a value for P3.15.1 Number of Motors 1...6
16
Set a value for P3.15.2 Interlock Function
0 = Not used
1 = Enabled
17
Set a value for P3.15.4 Autochange
0 = Disabled
1 = Enabled
If you enable the Autochange function, you see the next 3 questions. If you do not use the
Autochange function, the wizard goes directly to question 21.
WIZARDS VACON · 71