Table 50: Digital input settings
Index Parameter Default ID Description
P3.5.1.27 Timer 1 DigIN Slot0.1 447
The rising edge starts Timer 1 that
was programmed in Group 3.12.
P3.5.1.28 Timer 2 DigIN Slot0.1 448 See above.
P3.5.1.29 Timer 3 DigIN Slot0.1 449 See above.
P3.5.1.30 PID1 Setpoint Boost DigIN Slot0.1 1046
FALSE = No boost
TRUE = Boost
P3.5.1.31 PID1 Select Setpoint DigIN Slot0.1 1047
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.32 External PID Start Signal DigIN Slot0.2 1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter has no effect if the
external PID controller is not enabled
in Group 3.14.
P3.5.1.33 External PID Select Setpoint DigIN Slot0.1 1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.34 Motor 1 Interlock DigIN Slot0.1 426
FALSE = Not active
TRUE = Active
See Table 96 Multipump parameters.
P3.5.1.35 Motor 2 Interlock DigIN Slot0.1 427
FALSE = Not active
TRUE = Active
See Table 96 Multipump parameters.
P3.5.1.36 Motor 3 Interlock DigIN Slot0.1 428
FALSE = Not active
TRUE = Active
See Table 96 Multipump parameters.
P3.5.1.37 Motor 4 Interlock DigIN Slot0.1 429
FALSE = Not active
TRUE = Active
See Table 96 Multipump parameters.
PARAMETERS MENU VACON · 139