Table 50: Digital input settings
Index Parameter Default ID Description
P3.5.1.38 Motor 5 Interlock DigIN Slot0.1 430
FALSE = Not active
TRUE = Active
See Table 96 Multipump parameters.
P3.5.1.39 Motor 6 Interlock DigIN Slot0.1 486
FALSE = Not active
TRUE = Active
See Table 96 Multipump parameters.
P3.5.1.40 Reset Maintenance Counter DigIN Slot0.1 490
TRUE = Reset
P3.5.1.41 Enable DI Jogging DigIN Slot0.1 532
Enables the Jogging function from
digital inputs. Does not have an effect
on the jogging from fieldbus.
P3.5.1.42
Jogging Reference 1
Activation
DigIN Slot0.1 530
Connect to a digital input to activate
P3.3.6.4.
NOTE!
If the input is activated, the drive
starts.
P3.5.1.43
Jogging Reference 2
Activation
DigIN Slot0.1 531
Connect to a digital input to activate
P3.3.6.5.
NOTE!
If the input is activated, the drive
starts.
P3.5.1.44 Mechanical Brake Feedback DigIN Slot0.1 1210
Connect this input signal to the
auxiliary contact of the mechanical
brake. If the contact is not closed
within the given time, the drive shows
a fault.
P3.5.1.45 Fire Mode Activation OPEN DigIN Slot0.2 1596
Activates the Fire mode if it is
enabled with a correct password.
FALSE = Fire Mode active
TRUE = No action
P3.5.1.46 Fire Mode Activation CLOSE DigIN Slot0.1 1619
Activates the Fire mode if it is
enabled with a correct password.
FALSE = No action
TRUE = Fire Mode active